Equal Percentage Valves - Opening Vs Flow
technologist | 23 Apr, 2009, 01:39 | General | (324 Reads)
In case of equal percentage valves, the flow varies according to the following definition.

'Any % change in the opening from its current existing value changes the flow by same percentage of its current value at current opening.'

Means if current opening is say 10% & u change it to 15% than the change in opening from its current value (of 10%) is 50%, so the flow will also increase by 50% of its existing value at 10% opening. This means if flow was say 20% of the total range (Or capacity of the valve) at 10% opening it will become 30% (50% higher compared to 20%) of the total range.